Inverter size calculator

Add the loads you want on backup, set how much runs at once, and get a planning continuous/surge range. Geysers and stoves often dominate.

Add loads you want on the inverter. Surge watts matter for motors (fridge, pumps, well pumps, A/C).

Results

Continuous need
—
Surge need
—
Suggested continuous
—
Suggested surge
—
Planning range
—

Methodology

Continuous need = sum(continuous watts × quantity) × simultaneous factor. Surge need ≈ continuous need + largest (surge − continuous) adder. Suggested rating applies safety headroom.

Worked example

Fridge 150 W (surge 600 W) + lights 100 W, simultaneous factor 1.0 and 25% headroom → continuous need 250 W → suggested continuous about 300–350 W class, with surge covering the fridge start adder.

Assumptions and limitations

Does not size DC solar input, battery C-rate, cable thickness, earth leakage or SANS compliance. Motor nameplate data varies.

Prefer critical-load panels for load-shedding. Whole-house backup often needs far larger inverters and batteries.

FAQ

Continuous vs surge?

Continuous is steady running watts. Surge covers short motor starts. Both matter.

Can I run a geyser on a small inverter?

Usually not — a 3 kW geyser alone needs a large continuous rating and battery.

Is this final design?

No. An installer must verify.